Tuesday, November 19, 2013

NATIONWIDE DISASTER SPECIALIST : WATER DAMAGE EXPERT RICH PIERI ON BUILDING DEHUMID...

NATIONWIDE DISASTER SPECIALIST : WATER DAMAGE EXPERT RICH PIERI ON BUILDING DEHUMID...: DRYING OUT BUILDINGS CALL 1-877-71-FLOOD Excess water content in materials Dehumidification is mainly applied to dry out excess water conten...

DRYING OUT BUILDINGS

Excess water content in materialsConstruction Of BuildingDehumidification is mainly applied to dry out excess water content in materials in connection with construction work or water damage.
In case of water damage the general rule is to apply dehumidification as soon as possible, but as the nature and extent of water damage varies considerably it is necessary to assess the right approach from situation to situation.
An all important parameter in case of water damage is how much time the water has had to penetrate the building structure, furnishings, etc. It is also essential to keep the air change as low as possible to avoid humid air from entering the room. The rules of thumb will give you some empiric data to go by as it is often almost impossible to calculate the absolute accurate dehumidification load needed in a water damage situation.
In case of drying out a newly constructed building you should also keep air change low, but the most important parameter to consider is the water content in the various materials used. Often you have to meet a deadline i.e. you have to consider a finite amount of time to do the job.
Drying out buildingsFormerly construction work on an average building went on for 6-9 months and the building materials were usually dried out by natural ventilation by the time the building was finished. Today, however, construction work is very efficient and much faster. This means that dehumidification is required to remove the excess water in the various building materials before the building can be occupied.
When selecting a dehumidifier for drying out a building you need to consider how much water should be removed and how much time you have to do it.
This is actually quite a difficult task. In some cases it is possible to estimate the amount of water in the building materials from tables. Please note that in regards to drying out a newly constructed building it all comes down to the specific building materials used for walls, floors and roofs. The water content of various building materials differ so much that a simple rule of thumb is unworkable.

Water content of different building materials (kg/m3)
MATERIALAT START OF PROJECTWATER CHEMICALLY BOUNDDESIRED CONDITION AT 50% RHWATER TO BE DEHUMIDIFIED
Wood80 -4040
Tile, roof10-100
Brick, wall80-1070
Lightweight concrete 100-200-2080-180
Concrete K 15 II1804238100
Concrete K 25 II180574677
Concrete K 40 II180715158

In this example we want to calculate the dehumidification load required to dry out excess water from a newly constructed building in 30 days. The building is 2.4 m high, 7 m wide and 16 m long. The walls and ceiling are constructed from pre-dried wood. The floor, however, needs to be dried out as it is made from 10 cm thick concrete, K 40 II.
The data:
Period30 days
Drying conditiont = 20°C and 50% RH (average between starting humidity at 60% RH and ending at approx. 40% RH)
Volume of building2.4 * 7 * 16 = 268.8 m3
MaterialsConcrete K 40 II, 10 cm

The calculation:
Concrete volume to be dehumidified:
V = 16 * 7 * 0.1 = 11.20 m3
Water content in concrete floor:
Q = 11.20 * 58 kg water/m3 = 649.6  kg water
We need to remove 649.6 L water in 30 days:
W = 649.6/30 = 21.65 L/24 hours
We need a dehumidification capacity of 21.65 L/24 hours.
Recommendation: CDT 40. Capacity: 0.70 litre/hour at 20°C/50% RH. One CDT 40 will remove 16.8 L/24 hours. This means that two CDT 40 units should do the job.
Read about Dantherm's mobile dehumidifiers CDT
Note that the drying process is quickest in the beginning as the water content is very high when you start the process. As the RH-value decreases the overall dehumidification capacity will also decrease.
Guidelines for the drying process
When dehumidification is used to dry out buildings and materials the dehumidifier runs continuously. The relative humidity is gradually lowered allowing further evaporation from the damp materials in the room. The amount of evaporation depends on the temperature of the room, the materials and the humidity of the air.
One of the advantages of condense drying is that the drying process is stable and gentle. If time is not of the essence the optimum dehumidification process is achieved by maintaining a stable condition of 20°C and approximately 40% RH in the room. This way you maintain a perfect balance between the dry air in the building and humid building materials, avoiding surface drying and cavitation as well as damage to pre-dried materials such as parquet floors.
Add heat if necessary, but keep in mind that forcing the drying process might be harmful. There is a risk of surface drying and cavitation, with only surfaces being dried, whereas a lot of humidity remains within cavities inside the wall. This prolongs the drying period as the humidity will not easily penetrate the dry surface. Surface drying also involves the risk of cracks appearing in the surfaces of walls, ceilings and floors.
It is important that the room/building is as sealed as possible. Also make sure that the building is well protected against rain and snow. You need to ventilate while painting inside the building, but remember to seal the room or building properly when it is empty. Also remember to avoid pre-dried materials absorbing water because of open windows.
If the air change inside the room is not controlled, then changing ambient temperatures and humidities make the process much more difficult to control. In the winter the cold outside air will normally contain a minimum of water and the humidity is not likely to increase much even if the air change is considerable. Energy consumption, however, will increase dramatically as you need to heat up the cold incoming air. In the summer the water content could be quite high and you will have to remove even more water from the building or locale if it is not sealed off adequately.
In most cases the humidity is concentrated in cellars and in areas where water is being used in the construction work going on i.e. painting, 

No comments: